In this paper, the nonlinear interaction of regular water waves propagating over a fixed and submerged circular cylinder is numerically studied. At the structure’s lee side, the free surface profile experiences strong nonlinear deformation where the superharmonic free wave generated can be significant and is superposed on the transmitted wave. The wave profile then becomes asymmetric and skewed and may eventually reach the point of physical wave breaking. The governing equation and boundary conditions of this wave–structure interaction problem are formulated using both the fully nonlinear and the weak-scatterer theory. The corresponding boundary value problem is numerically solved by the immersed-boundary adaptive harmonic polynomial cell solver. In this study, a pragmatic wave-breaking suppression model is incorporated into the original solver. Both the harmonic free wave amplitudes at the structure’s lee side and the harmonic vertical forces on the cylinder are studied. The simulated harmonic wave amplitudes are compared to other published experiments and theoretical data. In general, good agreement is achieved. The effects of the incorporated wave-breaking suppression model on the simulated results are discussed. In our study, the incorporation of the pragmatic wave-breaking suppression model successfully extends the capabilities of the original fully nonlinear immersed-boundary adaptive harmonic polynomial cell solver.
This paper investigates the challenges associated with remote harmonic compensation in offshore wind power plants through long cables and transformers. The interaction between the grid network and the wind power plant network can lead to the amplification of certain harmonics and potentially resonant conditions. Hence, the plant developer is required to maintain the harmonic distortion at the point of common coupling within the planning level limits using harmonic compensation, which is usually done by static filters. In this paper an active damping compensation strategy with a STATCOM using emulation of using emulation of resistance at the harmonic frequencies of concern is analyzed. Finally the results are demonstrated using time domain simulations in PSCAD.
When an offshore wind power plant is connected to the grid, there is a risk of amplification of certain harmonics and appearance resonances at the point of connection due to the interaction between the grid network and the wind power plant network. Hence, the plant developer is obliged to maintain the harmonic distortion at the point of common coupling within the planning level limits using harmonic compensation, which is usually done by passive filters. In this paper a novel active harmonic compensation technique using voltage feedback from a non-local bus has been proposed and analyzed. Its effectiveness has been demonstrated through real time simulations on a test system model.
Due to the presence of long high voltage cable networks, and power transformers for the grid connection, the offshore wind power plants (OWPPs) are susceptible to harmonic distortion and resonances. The grid connection of OWPP should not cause the harmonic distortion beyond the permissible limits at the point of common coupling (PCC). The resonance conditions should be avoided in all cases.
This paper describes the harmonic analysis techniques applied on an OWPP network model. A method is proposed to estimate the harmonic current compensation from a shunt-connected active power filter to mitigate the harmonic voltage distortion at the PCC. Finally, the harmonic distortions in the compensated and the uncompensated systems are compared to demonstrate the effectiveness of the compensation.
Various sources of harmonic problems in large wind power plants (WPPs) and optimized harmonic mitigation methods are presented in this paper. The harmonic problems such as sources of harmonic emission and amplification as well as harmonic stability are identified. Also modern preventive and remedial harmonic mitigation methods in terms of passive and active filtering are described. It is shown that WPP components such as long HVAC cables and park transformers can introduce significant low-frequency resonances which can affect wind turbine control system operation and overall WPP stability as well as amplification of harmonic distortion. It is underlined that there is a potential in terms of active filtering in modern grid-side converters in e.g. wind turbines, STATCOMs or HVDC stations utilized in modern large WPPs. It is also emphasized that the grid-side converter controller should be characterized by sufficient harmonic/noise rejection and adjusted depending on WPPs to which it is connected.